VC5 Controller Switching On and Off With In-Sight D900 Unit Connected

You must not use 24V power over the IO cable and PoE at the same time in this setup.

2025. 02. 07.

Question

My VC5 keeps restarting, and I have a In-Sight D900 series sensor connected to it.

Answer

This is a known effect that happens when you have the In-Sight D900 powered via 24V *and* PoE. The simplest fix is to remove the 24V power from the IO cable.

When a PoE connection is used, the In-Sight D900 multifunction port GND terminal will be at a voltage derived from the PoE voltage that is VERY different from the power ground of the PC host / VC5 / VC200 that is supplying PoE. Any connection between the In-Sight D900 multifunction port GND and the host ground will cause a problem.

If you connect an isolated 24V supply to the PWR and GND of the In-Sight D900 and make no other connections to that supply, the sensor will be powered and operate properly regardless of whether a PoE or non-PoE ethernet connection is present, as implied by the In-Sight D900 manual page 21. However, that supply will be a temptation for someone to make a connection to it for some other encoder, sensor, or other device and inadvertently create a connection to host ground, compromising the isolation and causing a problem.