Pass/Fail Bit Does Not Sent Via Industrial Protocol When Using an In-Sight Explorer Camera in EasyBuilder View

This article describes the typical reason if the Job Pass bit is not transferred through industrial protocol to the PLC from an EasyBuilder job.

2025. 03. 30.

Details

Issue:

The Job Pass bit is not transferred through industrial protocol to the PLC from an EasyBuilder job.
 

Causes:

The industrial protocol hasn't been added to the Communication Devices list in the EasyBuilder job.
 

Resolution:

  1. Click on the Communication Application Step:

    Placeholder
  2. Click on the Add Device button and select the industrial protocol that is used:

    Placeholder
  3. The selected protocol should appear in the Communication Devices list:

    Placeholder