Skip to Main Content
Cognex 지원 허브
LogoLogo

In-Sight D900 PROFINET "Inspection Completed" Bit is Not Toggled

Steps to fix issue with "Inspection Completed" bit in PLC module not toggling upon inspection

2024. 09. 15.

Details

The most common cause of the Inspection Complete bit failing to toggle is the lack of a "WriteResultsBuffer" function in the spreadsheet.  Make sure to add a "WriteResultsBuffer" function in your spreadsheet (the buffer can be empty) to ensure the bit is toggled.

관련 자원